[foxboro] Fw: FBI10E Block not visible from SMDH

Problem with the I/A slot.....moved to a different slot ..Now working 
fine.

Thx again for all the help
__________________
Thanks and Regards 
Ajit Kumar 

----- Forwarded by Ajit S Kumar/Technical/SAMREF/SA on 16/12/2007 04:43 PM 
-----

"Gillis, Dale" <Dale.Gillis@xxxxxxxxxxxxx> 
26/11/2007 04:54 PM

To
<Ajit.S.Kumar@xxxxxxxxxxxxx>
cc

Subject
RE: [foxboro] FBI10E Block not visible from SMDH






Try changing your letterbug to something entirely new and rebuild the ECB 
for the FBM and see if that worksâ?¦.more than once Iâ??ve run into bad 
Letterbug or Bad Hood Connectors.  Sorryâ?¦â?¦.I donâ??t read emails when Iâ??m 
off for the weekend!  Hope this helps you.
 

From: Ajit.S.Kumar@xxxxxxxxxxxxx [mailto:Ajit.S.Kumar@xxxxxxxxxxxxx] 
Sent: Saturday, November 24, 2007 11:12 AM
To: Gillis, Dale
Cc: foxboro@xxxxxxxxxxxxx
Subject: Fw: [foxboro] FBI10E Block not visible from SMDH
 

Dale, 
Tried its still not visible from SMDH.... 
Any help will be highly Appreciated...
__________________ 
Thanks and Regards 
Ajit 

----- Forwarded by Ajit S Kumar/Technical/SAMREF/SA on 24/11/2007 06:11 PM 
----- 

"Gillis, Dale" <Dale.Gillis@xxxxxxxxxxxxx> 
Sent by: foxboro-bounce@xxxxxxxxxxxxx 
22/11/2007 06:08 PM 


Please respond to
foxboro@xxxxxxxxxxxxx



To
<foxboro@xxxxxxxxxxxxx> 
cc
 
Subject
Re: [foxboro] FBI10E Block not visible from SMDH
 


 
 




For the System to see the new ECB Block you've created you have to have
this new FBM Physically connected to the CP60...that is in a Rack with a
hood connector and a Good Letterbug.  Then System Management will see
the new Block you've created.


Dale


-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx]
On Behalf Of Ajit.S.Kumar@xxxxxxxxxxxxx
Sent: Thursday, November 22, 2007 10:59 AM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] FBI10E Block not visible from SMDH

Hello ,
I have configured a ECB Block for FBM1...
But its not visible in SMDH, Its a CP60 which has FBI10E and 100 Series=20
FBMs,

Note : In this CP we have two FBI10E Configured.

Following were tried...
Delete / Undelete were tried but not successful.
Deleted the block and recreated still not possible.

Do I need to Download All from the same CP , The plant is running so I
do=20
not want to take the risk.

Appreciate your help and thanks in advance


Regards

Ajit - SAMREF

=20
=20
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
=20
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin
to unsubscribe:      =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave
=20


_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html

foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: