[foxboro] FoxCAE Loadall problem.

Hi all,
I am facing some problems related to LoadAll disk made from FOXCAE. I
was given an existing Database already imported to FOXCAE. I added few
things and took export to diskette. I had selected UNIX option in
FOXCAE while exporting.

 When I reached site and tried to make a LoadAll disk using mk_loadll
utility, it pounded me with tons of errors. Almost every single block
in each compound had errors. Mostly the error was "FAIL
CMPNAME:BLKNAME - Invalid End zone for block type CIN "  ( or
AIN....). I had used the same procedure plenty of times at another
site but never had faced this problem.

To analyze further, I compared the compounds on diskette containing
original saveall with the the one exported from FOXCAE. (This compound
was not touched while doing work for other compounds, so it was a nice
example for comparison).  It appears to me that FOXCAE has deleted few
lines like - END_ECB_ZONE etc. and this is the root cause of errors. I
am pasting both the compound contents for comparison. Does anyone know
a fix?



------ Content of old compound, from saveall disk at site---------

NAME     >24BA_001
TYPE     >COMPND
DESCRP   >
PERIOD   >3
PHASE    >1
ON       >1
INITON   >2
CINHIB   >4
GR1DV1   >2WPDB1
GR1DV2   >2WPDB2
GR1DV3   >2WP0B3
GR1DV4   >
GR1DV5   >histb1
GR1DV6   >LP01
GR1DV7   >
GR1DV8   >
GR2DV1   >
GR2DV2   >
GR2DV3   >
GR2DV4   >
GR2DV5   >
GR2DV6   >
GR2DV7   >
GR2DV8   >
GR3DV1   >
GR3DV2   >
GR3DV3   >
GR3DV4   >
GR3DV5   >
GR3DV6   >
GR3DV7   >
GR3DV8   >
LOOPID   >
NAME     >-END_ECB_ZONE
NAME     >BA_001
TYPE     >CIN
DESCRP   >24H003 - IGNITOR  ON
PERIOD   >3
PHASE    >1
LOOPID   >31040.9
IOMOPT   >0
IOM_ID   >
PNT_NO   >0
ANM      >BA_001
NM0      >OFF
NM1      >ON
IVO      >0
MA       >1
INITMA   >1
INHOPT   >0
INHIB    >0
INHALM   >0x0
INVALM   >0
MANALM   >0
SAO      >0
SAP      >2
SAG      >1
BAO      >0
BAT      >INPUT
BAP      >2
BAG      >1
SCOPT    >0
SCGRP    >1
SCTXT0   >OFF
SCTXT1   >ON
PROPT    >0
IN       >24DI_SCAN1:DI_31039.CIN_25
NAME     >-END_CONT1_ZONE
NAME     >-END_SEQ_ZONE
NAME     >-END_CONT2_ZONE
NAME     >-END_DATA_ZONE
NAME     >END
**** Revision Code 1015

 ------------------Content of Same compound from FOXCAE Loadall Export
Disk----------
NAME     >24BA_001
TYPE     >COMPND
DESCRP   >
PERIOD   >3
PHASE    >1
ON       >1
INITON   >2
CINHIB   >4
GR1DV1   >2WPDB1
GR1DV2   >2WPDB2
GR1DV3   >2WP0B3
GR1DV4   >
GR1DV5   >histb1
GR1DV6   >LP01
GR1DV7   >
GR1DV8   >
GR2DV1   >
GR2DV2   >
GR2DV3   >
GR2DV4   >
GR2DV5   >
GR2DV6   >
GR2DV7   >
GR2DV8   >
GR3DV1   >
GR3DV2   >
GR3DV3   >
GR3DV4   >
GR3DV5   >
GR3DV6   >
GR3DV7   >
GR3DV8   >
LOOPID   >
NAME     >BA_001
TYPE     >CIN
DESCRP   >24H003 - IGNITOR  ON
PERIOD   >3
PHASE    >1
LOOPID   >31040.9
IOMOPT   >0
IOM_ID   >
PNT_NO   >0
ANM      >BA_001
NM0      >OFF
NM1      >ON
IVO      >0
MA       >1
INITMA   >1
INHOPT   >0
INHIB    >0
INHALM   >0
INVALM   >0
MANALM   >0
SAO      >0
SAP      >2
SAG      >1
BAO      >0
BAT      >INPUT
BAP      >2
BAG      >1
SCOPT    >0
SCGRP    >1
SCTXT0   >OFF
SCTXT1   >ON
PROPT    >0
IN       >24DI_SCAN1:DI_31039.CIN_25
NAME     >END
**** Revision Code 1015

Thanks in advance

Hitesh
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: