Subject: Micro I/A Ver.6.2.1 MODBUS problem. We have installed the new Micro I/A ver. 6.2.1 image at Lever Ponds on Saturday. All the analog feed backs we received from a Schenk PLC (MODBUS protocol) were incorrect. Sunday morning 4am, we had to re-load Ver.6.2RA. This fixed the problem. WORK DONE BEFORE TESTING. 1) SaveAll 2) Initialize, reboot and LoadAll. 3) Rebuild ECB109 4) Check LONG_S in blocks FIIN and FIOUT SYSTEM CONFIG. * AW51D * 2 X Micro I/A (Modbus) * 2 X CP60 * 6 X CP30 * 1 X CLI * 6 X X-Terms We need to know what to do to fix this problem, because the customer does not want to run a beta version. If you need more info, please contact me. Best Regards Deon Kriel Protea Automations Solutions Tel. : +27 11 719-5740 Fax : +27 11 887-8757 Cell : +27 82 575-9908 _____ This e-mail message has been scanned for Viruses and Content and cleared by MailMarshal - For more information please visit <http://www.marshalsoftware.com> www.marshalsoftware.com _____ ##################################################################################### This e-mail message has been scanned for Viruses and Content and cleared by MailMarshal For more information please visit www.marshalsoftware.com ##################################################################################### ___________________________________________________________________ This list is neither sponsored nor endorsed by The Foxboro Company. Use the information obtained here at your own risk. For disclaimer, see http://www.thecassandraproject.org/disclaimer.html#maillist list info: //www.freelists.org/list/foxboro subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave