We have faced similar problems, and in certain cases rebooting one of
The FT pairs could resolve the problem . One of the probable reasons
Could be the CP going out of resources (IPC channels not available) .
You May investigate further using rsipc utilities .
GOPS
Aramco Mobil Refinery
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On
Behalf Of Deo, Terry
Sent: Saturday, November 15, 2003 3:22 AM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] Cyan Displays
We had a rather unusual event earlier this week and I was hoping that
someone might have seen something similar and can offer some
explanation. I was called by our field supervisor who told me that the
workstations on all 4 of our nodes (which are connected via a carrier
LAN) were getting cyan connections when displays were called. I called
up a stations display from a CP to an AW both on another node and it
also displayed cyan connections. After checking the system I found a CP
that was failed in system management but was still "green" at the
modules. When this CP was rebooted all of the problems stopped and
everything has run fine since. The thing that is particularly curious
is how a failed CP could cause errors across several nodes.
Any information about a similar problem or any ideas on how this could
happen would be greatly appreciated.
Regards,
Terry
Terry J. Deo
Process Control Systems Engineer
Infineum USA, L.P.
Bayway Chemical Plant
Linden, New Jersey
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts: