[foxboro] CFT10 on a FBM43

Hi all


I have a CFT10 Mass Flow Transmitter and I want to hook it up to a FBM43.  I'm 
running P91 Version 8.3 Software and it is hanging off a FCP270 FT Pair. After 
reading the manuals B0193AW I can only find an ECB22 for a CFT10 and I think 
this is when you hang it off the PIOBUS which I'm not doing.  I would rather 
use the 4 to 20 mA Signal as an input to the FBM43.  I have 6 other channels 
working on this FBM with FoxComm Transmitters in Digital Mode 4800 BAUD and 
they work fine.  When I make my CFT10 a Child (ECB18) of this FBM43 it looks 
like it communicates and it goes online ok but I cannot talk to it with IFDC 
which is on the same BOX (P91).  I keep getting the following errors : over and 
over again...........Any help or guidance would be greatly appreciated.


3/20/2009  7:07:25 PM.500 >>>>---------------------
PARAMETER READ ERROR!!
Sizes do not match.
Parm: C_REVMAJ  Expected size: 4  Received size: 255PARAMETER READ ERROR!!
Sizes do not match.
Parm: EGUNAM1  Expected size: 6  Received size: 255

3/20/2009  7:07:37 PM.484 >>>>---------------------
PARAMETER READ ERROR!!
Sizes do not match.
Parm: EGUNAM1  Expected size: 6  Received size: 255

3/20/2009  7:07:49 PM.484 >>>>---------------------
PARAMETER READ ERROR!!
Sizes do not match.
Parm: EGUNAM1  Expected size: 6  Received size: 255

3/20/2009  7:08:01 PM.484 >>>>---------------------
PARAMETER READ ERROR!!
Sizes do not match.
Parm: EGUNAM1  Expected size: 6  Received size: 255

3/20/2009  7:08:13 PM.484 >>>>---------------------
PARAMETER READ ERROR!!
Sizes do not match.
Parm: EGUNAM1  Expected size: 6  Received size: 255

3/20/2009  7:08:25 PM.484 >>>>---------------------
PARAMETER READ ERROR!!
Sizes do not match.
Parm: EGUNAM1  Expected size: 6  Received size: 255

3/20/2009  7:08:37 PM.500 >>>>---------------------
PARAMETER READ ERROR!!
Sizes do not match.
Parm: EGUNAM1  Expected size: 6  Received size: 255

  
Dale Gillis
Newpage Corporation
120 Pulpmill Road
Point Tupper
PO Box 9500
Port Hawkesbury 
Nova Scotia, Canada
B9A1A1
This electronic message contains information from NewPage Corporation or 
subsidiary companies, which may be confidential, privileged or otherwise 
protected from disclosure. The information is intended to be used solely by the 
recipient(s) named. If you are not an intended recipient, be aware that any 
review, disclosure, copying, distribution or use of this transmission or its 
contents is prohibited. If you have received this transmission in error, please 
notify NewPage immediately at postmaster@xxxxxxxxxxxxxxxx

 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: