[foxboro] Alarm Manager Colors
- From: José Luis Molina <molina@xxxxxxxxxxxx>
- To: foxboro@xxxxxxxxxxxxx
- Date: Fri, 30 Jan 2004 10:09:09 -0300
Hi list,
we have a I/A Series 6.5 system with FoxView 8.0 running on AW70's,
WP70's
and a couple of AW51D's. The Alarm Manager is v1.0 according to the
"Help/About..."
The operators use AW70's and WP70's (not the AW51's).
We want to use 2 priority levels for alarms: 1 (red) and 2 (yellow).
Green
for "return to normal" alarm.
The thing is: for ACKed alarms we have "static yellow" and "static
green",
but for UNACKed alarms there is no "blinking yellow" and no "blinking
green" available on the AM (at least, I didn't find them).
According to the AM Help, on 51's it is possible to define blinking
properties to colors, but for 70's there is no such thing: there is
"blinking red", "blinking magenta" and a few others, but not the ones we=
want.
Is there a walkaround to redefine the palette on 70's stations?
TIA,
joseluis
_____________________________________________________________________
MOLINA, Jos=E9 Luis =20
Nuclear Engineer =20
E-mail: molina@xxxxxxxxxxxx =20
=20
INVAP S.E. =20
Address: Moreno 1089 Phone: +54 (2944) 422121 =20
(8400) Bariloche - RN Fax: +54 (2944) 423051 =20
ARGENTINA
_____________________________________________________________________
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts:
- » [foxboro] Alarm Manager Colors