[foxboro] AW51B boot problem
- From: "Cyrus W. Taft" <cwtaft@xxxxxxxxxxxxxx>
- To: Foxboro Mailing List <foxboro@xxxxxxxxxxxxx>
- Date: Thu, 22 Jul 2004 16:46:28 -0400
I am having a problem getting the AW51B, ver. 6.1, on my ESSCOR simulator=
to boot. It has the following messages:
Timeout waiting for ARP/RARP packet
Lost carrier (transceiver cable problem?)
Cable problem or twisted pair hub link-test disabled
Typing 'test net' at the ok prompt showed that the AUI ethernet port was
functioning properly but the TPE port failed the external loopback test. =
The AUI port is the second ethernet port to a plant lan, and the TPE port=
goes to the DNBI. I have checked cables and see no obvious problems. =
There appear to be two connectors available for the TPE port. One is som=
e
kind of a Sun specific connector and the other is the standard twisted pa=
ir
type of connector. The DNBI cable is connected to the Sun connector. If=
I
connect the plant lan cable to the twisted pair connector and rerun the
test net, the TPE port shows good. The AW module in the DNBI rack has a
green light on it but that's about all I know about it. Any ideas on oth=
er
things I might check to figure out where this problem is? Thanks for any=
help.
Cyrus Taft
EPRI I&C Center
. =
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
- Follow-Ups:
- Re: [foxboro] AW51B boot problem
- From: Janet Parker
Other related posts:
- » [foxboro] AW51B boot problem
- Re: [foxboro] AW51B boot problem
- From: Janet Parker