[foxboro] AW51B boot problem

I am having a problem getting the AW51B, ver. 6.1, on my ESSCOR simulator=

to boot.  It has the following messages:

Timeout waiting for ARP/RARP packet
Lost carrier (transceiver cable problem?)
Cable problem or twisted pair hub link-test disabled

Typing 'test net' at the ok prompt showed that the AUI ethernet port was
functioning properly but the TPE port failed the external loopback test. =

The AUI port is the second ethernet port to a plant lan, and the TPE port=

goes to the DNBI.  I have checked cables and see no obvious problems. =

There appear to be two connectors available for the TPE port.  One is som=
e
kind of a Sun specific connector and the other is the standard twisted pa=
ir
type of connector.  The DNBI cable is connected to the Sun connector.  If=
 I
connect the plant lan cable to the twisted pair connector and rerun the
test net, the TPE port shows good.  The AW module in the DNBI rack has a
green light on it but that's about all I know about it.  Any ideas on oth=
er
things I might check to figure out where this problem is?  Thanks for any=

help.

Cyrus Taft