[foxboro] AW: Alarm panel

The entries in our AAtab files are sorted.

Andreas

-----Urspr=FCngliche Nachricht-----
Von: JL Joachim Leuker [mailto:Joachim_Leuker@xxxxxxxxxxxxxxxxx]
Gesendet: Donnerstag, 31. Oktober 2002 12:22
An: foxboro@xxxxxxxxxxxxx
Betreff: Re: [foxboro] Alarm panel



Hello, Bram,

thank you for your answer. It is a first entry for discussion and thus
helpful.

I think we have gone through all the issues you mention, but I will =3D
inspect
them again.

The "defective" AAtab file seems ok to me, but:
- It has no empty line at the end and
- the entries are unsorted with respect to panel and key numbers.
Is this really ok?

Not "correctly" means, that the panels do work but they blink where =3D
there is
no alarm.

Thank you again, regards
Joachim Leuker

--
Dr. Joachim Leuker - Client Manager
Actemium - HMS Planung & Automation GmbH
Duisburg, Germany
http://www.actemium.de
ACTEMIUM - A BRAND OF GTIE

-----Urspr=3DFCngliche Nachricht-----
Von: Marsman, Bram [mailto:bmarsman@xxxxxxxxxxx]
Gesendet am: Donnerstag, 31. Oktober 2002 10:57
An: 'foxboro@xxxxxxxxxxxxx'
Betreff: Re: [foxboro] Alarm panel


Hi Joachim,

I will answer you although it probably doesn't help much!
My experience has always been that increasing MAX_ACTIONS works, on =3D
both NT
and UNIX, in init.user.
So, here are some obvious things, maybe you overlooked one....

- Did you reboot?
- Did you remove the # in front of MAX_ACTIONS
- Did you perhaps add you "own" MAX_ACTIONS and is it overwritten later =
=3D
in
the file?
- Even more stupid suggestion: Did you perhaps changed init.user.rel in
stead of init.user?

You say the panels do not work "correctly". Do they work at all? Do =3D
they
only work for blocks 1-2000? Are there any syntax errors in your AAtab
files?

As a last resort: You could try to change MAX_ACTIONS in wp51_glbls, =
=3D
however
this has never been necessary in my experience, besides its "illegal". =
=3D
(own
risk etc)

Good Luck,
Bram Marsman
Invensys Systems Netherlands.

=20
=20
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
=20
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin
to unsubscribe:      =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave
=20
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: