[foxboro] ABGateway, AW51 w/AB PLC, and MCIN blocks

Hey Everybody,

Long time no post!  (Which means things are good, I guess.)

I have run across an unusual problem and thought some of you might have 
already seen/solved it.

Here's the background...
I am building some displays for use with a lot of MCIN blocks coming from a 
ABGW30.  These FoxView displays lend themselves to using the BITSTATE 
parameters and OR ing several bits together for some fill colors. Typically 
I would do this with the PAKCIN parameter.  Of course, the bytes are 
reversed coming from the PLC unless you set the IOMOPT=3 of the MCIN.

Here's the problem...
We are using a simulator to test the displays/control before we put this 
into a production system.  The simulator uses a AW51 with Interchange to 
connect via ethernet to the PLC.  The PAKCIN seems to exhibit the same 
problem of having the bytes swapped, BUT I can't get the MCIN to accept an 
IOMOPT = 3 so I can't swap the bytes (easily, without using more 
blocks).  Has anyone seen this before?

Any advice would be appreciated.

Regards,
David Johnson

PREMIER System Integrators
Phone:  (256) 355-1732
Fax:    (256) 355-9088
Email   David.Johnson@xxxxxxxxxxxxxxxxxx

 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: